HOSPITAL UNISZA PATHOLOGY LABORATORY

Client Challenges

Unable to achieve room parameters

Unable to control the Air-conditioning system

Condensation

High number of Bio safety cabinet

High exhaust air flow

Seaside condition

Strong wind

Air infiltration via doors and Bio safety cabinet

Create a very strong draft when the BSCs are running

NOTE: These AHUs are 100% fresh air 

Solution Provided

Install our ICON System

  • To compensate the pressure loss due to BSCs
  • To control the temperature and RH
  • To maintain a negative pressure in the lab.
  • To maintain a positive pressure in the Cell Culture Room

Install a control system to control the ICON units, AHUs and exhaust fans.

Results & Achievement

Temperature and RH are achieved

Room pressure is achieved

Room pressure is regulated such that the pressure is maintained no matter how many BSCs are running.